New Year Special 70% Discount Offer - Ends in 0d 00h 00m 00s - Coupon code: save70

Free and Premium Huawei H12-425 Dumps Questions Answers

Page: 1 / 9
Total 240 questions

HCIP-Data Center Facility Deployment Questions and Answers

Question 1

When turning on the maintenance bypass switch of UPS5000-E after the maintenance completed, to make sure loads continue to be powered, which of the following should be noted?

Options:

A.

The bypass module has no alarm, and input is normal.

B.

Even if the bypass module is abnormal, the maintenance bypass switch can be turn off.

C.

If the UPS is in EPO status, the maintenance bypass switch can be turned off

D.

The battery input is normal

Buy Now
Question 2

If the customer load cannot be power-off, what should be taken care when closing the maintenance bypass switch?

Options:

A.

The maintenance bypass switch can also be closed in the inverter power supply mode

B.

Turn off the inverter, let the UPS be in bypass power supply mode and then close the maintenance bypass switch

C.

First perform EPO then close maintenance switch

D.

Close the maintenance switch first and then execute the EP

Question 3

The cycle life of the battery is direct proportional to the depth of discharge

Options:

A.

TRUE

B.

FALSE

Question 4

NetCol5000-A100 kW is dual system air conditioner. One indoor unit has two compressors.

Options:

A.

TRUE

B.

FALSE

Question 5

FusionModule1000A series solution meets the TIER 4 requirements if it adopts 2N power supply and distribution system.

Options:

A.

TRUE

B.

FALSE

Question 6

Huawei NetCol5000-A line-level precision air conditioner mainly solves the hot issue of high-density data center

Options:

A.

TRUE

B.

FALSE

Question 7

In the water-side free cooling solution, cold water can be transported directly from the cooling tower to chilled water air conditioner.

Options:

A.

TRUE

B.

FALSE

Question 8

After all the NetEco monitoring cables are connected, users need to check ( ).

Options:

A.

Power cables and signal cables are bound separately.

B.

Proper redundancy is reserved at connectors of signal cables.

C.

Signal cable connectors are intact.

D.

Proper redundancy is reserved at the turning point for signal cables.

Question 9

NetCol5000-A25 kW indoor unit needs neutral wires.

Options:

A.

TRUE

B.

FALSE

Question 10

The height of the ECC800 collector is () U.

Options:

A.

1

B.

2

C.

3

D.

4

Question 11

Which component can control the light and charge a pad in FusionModule2000?

Options:

A.

Access actuator

B.

AC actuator

C.

Skylight actuator

D.

Smart ETH gateway

Question 12

Which components can be installed onto the guide rail?

Options:

A.

ETH converter

B.

Access actuator

C.

Skylight Actuator

D.

AC Actuator

Question 13

When ATS is in automatic mode, the handle for manual operation must be remove.

Options:

A.

TRUE

B.

FALSE

Question 14

The BCB-BOX provides overload and short-circuit protection as well as remote trip control.

Options:

A.

TRUE

B.

FALSE

Question 15

If IP21 component is configured, top cable routing is not supported for UPS5000-E.

Options:

A.

TRUE

B.

FALSE

Question 16

ECC800 supports two AC power inputs.

Options:

A.

TRUE

B.

FALSE

Question 17

UPS2000-G-(6-20kVA) without batteries can work in normal mode, but cannot transfer to battery mode.

Options:

A.

TRUE

B.

FALSE

Question 18

The humidifier that used in NetCol8000-A is ().

Options:

A.

Electrode humidifier

B.

Infrared humidifier

C.

Wet film humidifier

D.

High-pressure micro-mist humidifier

Question 19

When a backfeed occurs in main or bypass, the backfeed protection card can send signals to trip the input circuit breaker.

Options:

A.

TRUE

B.

FALSE

Question 20

Power segment function is enabled on UPS2000-G-20kVA. Which will cause the loads connected with PL terminals power- off?

Options:

A.

Overload

B.

Battery under voltage

C.

Mains input interruption

D.

Mains Under voltage

Question 21

The principle of the () humidifier is that the high-intensity infrared lamp causes the water surface to release water vapor and diffuse into the air stream that needs to be humidified.

Options:

A.

Electrode

B.

Wet film

C.

High pressure fogging

D.

Infrared

Question 22

FusionModule1000 is an indoor prefabricated all in-one data center solution.

Options:

A.

TRUE

B.

FALSE

Question 23

One NetCol520 chilled water distribution unit can support a maximum of ( ) NetCol5000-C

Options:

A.

12

B.

10

C.

8

D.

6

Question 24

The EPO ports of UPS5000-E can be selected to normal open or normal close.

Options:

A.

TRUE

B.

FALSE

Question 25

Whether the water distribution unit is equipped or not is based on installation scenarios

Options:

A.

TRUE

B.

FALSE

Question 26

Site selection is one challenge for the traditional data center

Options:

A.

TRUE

B.

FALSE

Question 27

NetCol5000-A25 kW uses as thermal expansion valve.

Options:

A.

TRUE

B.

FALSE

Question 28

The () port is not on the smart ETH gateway.

Options:

A.

PWR_IN

B.

PWR_OUT

C.

PoE

D.

AI/DI

Question 29

If UPS5000-E works in maintenance bypass mode, bypass module cannot work.

Options:

A.

TRUE

B.

FALSE

Question 30

When installing the power line on the UPS5000-E, if there are different sources on the main-lines and bypass, you need to remove the copper bars connected to the bypass and main lines first, and then connect the main circuit and bypass input respectively.

Options:

A.

TRUE

B.

FALSE

Question 31

What does ā€œEā€ stand for in UPS5000-E-120k-HASBS?

Options:

A.

208 V system

B.

E series modular UPSs

C.

Input switch type of ATS

D.

Input switch type of MCCB

Question 32

First time powering on UPS5000-E, make sure that the UPS main input switch, bypass switch, output switch, maintenance bypass switch and battery switch are all OFF

Options:

A.

TRUE

B.

FALSE

Question 33

DuringNetCol5000-C commissioning, the opening of the water valve needs to be adjusted to minimum when you inject water and exhaust air.

Options:

A.

TRUE

B.

FALSE

Question 34

ECC800 does not support wireless communications.

Options:

A.

TRUE

B.

FALSE C.

C.

Question 35

The compressor suction pressure of NetCol5000-A25kW is low. It is possible that ().

Options:

A.

The electric heater is burnt out

B.

The refrigerant is insufficient.

C.

There is water vapor in the pipe

D.

The condensing pressure is low.

Question 36

( ) can connect to the AI/DI port on the access actuator.

Options:

A.

IC card reader

B.

Fingerprint and card reader

C.

Exit button

D.

Magnetic

Page: 1 / 9
Total 240 questions